Contents
Chapter 3 — Hardware Setup
L
N
G
115 VAC Hot
115 VAC Neutral
Ground
+
Com
G
24 VDC +
24 VDC Common
Ground
Host & Slave Address
Add values of switches and then add 1 to total
to calculate address
Examples
SW
1
2
3
4
5
6
Value
1
2
4
8
16
32
Address 1
Address 8
6 5 4 3 2 1
6 5 4 3 2 1
(0+0+0+0+0+0)=0+1=1
(0+0+0+4+2+1)=7+1=8
ON
OFF
ON
OFF
HOST
SLAVE
8 7 8 7 8 7 8 7
Datalinks
A,D,C,D A&D only A only NONE
ON
ON
OFF
OFF
ON
OFF
8 7 6 5 4 3 2 1 8 7 6 5 4 3 2 1
Fault on Loss of
Modbus Plus
Global Database
Control
88
ON=Enable
OFF=Disable
77
ON=Enable
OFF=Disable
3 Hardware Setup
3.1 1560-MBP Card Setup
3.1.1 Connecting Power to the 1560-MBP Card
Connecting power requires a simple termination of the 120
VAC or 24 VDC cable to the front of the module. The
connections are shown in the following diagram:
3.1.2 Dip Switch Configuration
Configuration of the 1560-MBP consists of setting up some
dip switches. The dip switches are as follows:
Please note that dip switch configuration is read
by the 1560-MBP during the power up process.
Power must be cycled if dip switches are changed
under power.